您现在的位置是: 首页 > 家电维修 家电维修
空调技术规格书电子版_空调技术规格书
tamoadmin 2024-08-15 人已围观
简介1.谁能详细讲讲 空调中所说的 “过热度”“过冷度”是什么意思吗?有“排气过冷度”这种说法吗?2.空调压缩机接线u v x怎么接线图解这是c-sb453h8a涡旋压缩机的参数,50Hz power supply specifications modelsRefrigerant R22Out Put 6HPDisplacement 100.0cm3/revPower Source 3
1.谁能详细讲讲 空调中所说的 “过热度”“过冷度”是什么意思吗?有“排气过冷度”这种说法吗?
2.空调压缩机接线u v x怎么接线图解
这是c-sb453h8a涡旋压缩机的参数,
50Hz power supply specifications models
Refrigerant R22
Out Put 6HP
Displacement 100.0cm3/rev
Power Source 3Ph 50Hz (380,415)V
Compressor Code 809 860 88
Compressor Model C-SB453H8A
Nominal Capacity 17.7KW 60.4x1000BTU/h
Condensing Temperature 54.4℃/130℉
Evaporating Temperature 7.2℃/45℉
Liquid Temperature 46.1℃/115℉
Return Gas Temperature 18.3℃/65℉
60Hz power supply specifications models
Refrigerant R22
Out Put 6HP
Displacement 100.0cm3/rev
Power Source 3Ph 60Hz (440,460)V
Compressor Code 809 860 88
Compressor Model C-SB453H8A
Nominal Capacity 21.5KW 73.4x1000BTU/h
Condensing Temperature 54.4℃/130℉
Evaporating Temperature 7.2℃/45℉
Liquid Temperature 46.1℃/115℉
Return Gas Temperature 18.3℃/65℉
谁能详细讲讲 空调中所说的 “过热度”“过冷度”是什么意思吗?有“排气过冷度”这种说法吗?
根据国家标准《建筑物空气调节与通风设计规范》(GB 50736-2012),空调室外机噪音标准应符合以下要求:
1.在室外机的运行状态下,其噪声水平应符合当地环境噪声标准的要求。
2.在室外机的运行状态下,其噪声水平应符合国家标准《建筑物环境噪声标准》(GB 3096-2008)的要求。
3.在室外机的运行状态下,其噪声水平应符合制造商提供的技术规格书中的要求。
总之,空调室外机噪音标准应符合当地环境噪声标准和国家标准的要求,并且应符合制造商提供的技术规格书中的要求。
空调压缩机接线u v x怎么接线图解
你提的第一个问题,我不是很想回答;(因为经常没有回应)
看你是McQuay的,我就简单说说:
过热度:
在制冷系统中有“排气过热度”、“吸气过热度”两个关键点;
对于高压腔压缩机,需要同时控制“排气过热度”和“吸气过热度”两个参数;
对于低压腔压缩机,需要控制“吸气过热度”;
具体的控制幅度在压缩机厂家的技术规格书上面有建议,辅以平时工作当中的经验进行适当修正;
过冷度:
在制冷系统中指的是冷媒在冷凝器出口后面某一个点上制冷剂的状态,过冷度越大说明冷凝效果越好,或者冷媒量少;
过热度 = 温度 - 压力对应饱和温度
过冷度 = 压力对应饱和温度 - 温度
没有“排气过冷度”之说;
如果想进一步了解,可以去你们工厂的测试中心,找周工学一学
这是百度里的。借用一下。
U. V. W;分别对应接三相电源里的 黄,绿,红;三相。
注意:三相压缩机一般有转向要求,不能反转!
建议接好以后,短时间通电试一下。保证转向正确以后,再投入运行。